Service Concentric Cables

Service Concentric Cables

Concentric Cables With Copper Or Aluminum Conductors
600V Service Cable

Application

The Service Concentric Cables used at voltages of 600 volts and at conductor temperatures not to exceed 70°C for polyethylene (PE) and Polyvinyl chloride (PVC) insulated conductors or 90°C for cross-linked polyethylene (XLPE) insulated conductors.

● Conductor:Copper/Aluminum/8000 series Aluminum Alloy/Copper clad Aluminum
● Insulation: XLPE/PVC/PE
● Concentric Neutral:Copper/Aluminum/8000 series Aluminum Alloy/Copper clad Aluminum
● Sheath: PVC/XLPE/PE

Specifications

● SANS 1507-6 Electric cables with extruded solid dielectric insulation for fixed installations (300/500 V to 1 900/3 300 V)  Part 6: Service cables
● UL44 Standard For Safety Thermoset-Insulated Wires and Cables
● UL854 Standard For Safety Service-Entrance Cables
● PIESA 1062 Concentric Single-Phase Aerial Service Cable – For Domestic Service Connections With a Combined Neutral-Earth Conductor
● IEC 60502-1 Power Cables With Extruded Insulation And Their Accessories For Rated Voltages From 1 kV (Um = 1.2 kV) Up To 30 kV (Um = 36 kV) –Part 1: Cables For Rated Voltages Of 1 kV (Um = 1.2 kV) And 3 kV (Um = 3.6 kV)
● KS 04-1022 Kenya Standard Specification For 600/1000V PVC-Insulated Single-Phase Concentric Cables With Copper Or Aluminum Conductors For Electricity Supply

Parameter

AAAC-8000/XLPE/UV-XLPE UL854

Size Phase conductor Inner sheath* Neutral conductor Polyester tape Outer sheath Approx.
Overall dia.
Nominal D.C resistance at 20℃
No. of wire Dia. of wire Nominal
Insulation thickness
Nominal thickness No. of wire Dia. of wire Nominal thickness Nominal thickness
No. / AWG No. mm mm mm No. mm mm mm mm Ω/km
2 × #8 7 1.234 1.14 25 0.653 0.10 1.14 9.6 3.4464
2 × #6 7 1.555 1.14 25 0.813 0.10 1.14 11.1 2.1684
2 × #4 7 1.961 1.14 26 1.024 0.10 1.14 12.7 1.3633
3 × #6 7 1.56 1.14 1.0 65 0.511 0.10 1.52 13.5×20.4 2.1684
3 × #4 7 1.961 1.14 1.0 65 0.643 0.10 2.03 16.0×24.1 1.3633
3 × #2 7 2.474 1.14 1.0 65 0.813 0.10 2.03 17.8×27.5 0.8573
4 × #4 7 1.961 1.14 1.0 65 0.643 0.10 1.52 24.4 1.3633
4 × #2 7 2.474 1.14 1.0 65 0.813 0.10 2.03 29.1 0.8573
*:Two options based on client requirement, a) wrapping tape b) extrusion PVC inner sheath

AAAC-8000/XLPE/UV-PVC & CU/XLPE/UV-PVC UL44

Size Phase conductor Inner sheath* Neutral conductor Polyester tape Outer sheath Approx.
Overall dia.
Nominal D.C resistance at 20℃
No. of wire Dia. of wire Nominal
Insulation thickness
Nominal thickness No. of wire Dia. of wire Nominal thickness Nominal thickness
No. / AWG No. mm mm mm No. mm mm mm mm Ω/km
2 × #8 7 1.234 1.52 14 0.873 0.09 1.52 11.7 3.4464
3 × #6 7 1.555 1.52 1.0 20 1.070 0.09 1.52 13.5×20.4 2.1684
*:Two options based on client requirement, a) wrapping tape b) extrusion PVC inner sheath
CU/XLPE/UV-PVC
Size Phase conductor Inner sheath* Neutral conductor Polyester tape Outer sheath Approx.
Overall dia.
Nominal D.C resistance at 20℃
No. of wire Dia. of wire Nominal
Insulation thickness
Nominal thickness No. of wire Dia. of wire Nominal thickness Nominal thickness
No. / AWG No. mm mm mm No. mm mm mm mm Ω/km
2 × #8 7 1.234 1.14 25 0.653 0.09 1.14 9.6 2.10
3 × #8 7 1.234 1.14 1.0 65 0.405 0.09 1.14 15×19 2.10
3 × #6 7 1.555 1.14 1.0 65 0.511 0.09 1.52 16×20 1.32
3 × #4 7 1.961 1.14 1.0 65 0.643 0.09 1.52 18×22 0.830
*:Two options based on client requirement, a) wrapping tape b) extrusion PVC inner sheath

Aluminum/PVC/UV-PVC KS 04-1022

Size Phase conductor Neutral
conductor
Polyester tape Outer sheath Approx.
Overall dia.
Ma.D.C resistance at 20℃
Size No. of wire Nominal
Insulation thickness
Size Nominal thickness Nominal thickness
Phase Neutral
Communication
No. / mm² mm² No. mm mm² mm mm mm Ω/km Ω/km
1×10+23 10 7 1.55 23 0.05 1.4 12.21 3.08 1.335
1×16+26 16 7 1.55 26 0.05 1.4 13.34 1.91 1.808
1×25+29 25 7 1.60 29 0.05 1.5 14.88 1.20 1.0586
1×35+38.6 35 19 1.65 38.6 0.05 1.6 16.75 0.868 0.7966

CU/XLPE/UV-PE PIESA 1062

Size Phase conductor Neutral
Conductor Size
Concentric wires Polyester tape Outer sheath Approx.
Overall dia.
Ma.D.C resistance at 20℃
Size No. of wire Nominal
Insulation thickness
No. of cores Dia. of wire Nominal thickness Nominal thickness
Phase Neutral Communication
No. / mm² mm² No. mm mm² No. mm mm mm mm Ω/km Ω/km Ω/km
2×4 4 7 0.7 4 2 0.8 0.05 1.4 10.2 4.75 4.61 35
2×6 6 7 0.7 6 2 0.8 0.05 1.4 10.8 3.18 3.08 35
2×10 10 7 0.7 10 2 0.8 0.05 1.4 12.0 1.89 1.83 35
2×16 16 7 0.7 16 2 0.8 0.05 1.4 13.0 1.19 1.15 35
4*×4 4 7 0.7 4 2 0.8 0.05 1.6 15.0 4.75 4.61 35
4*×6 6 7 0.7 6 2 0.8 0.05 1.6 16.5 3.18 3.08 35
4*×10 10 7 0.7 10 2 0.8 0.05 1.6 18.5 1.89 1.83 35
4*×16 16 7 0.7 16 2 0.8 0.05 1.6 21.0 1.19 1.15 35
Note:

  1. phase conductor shall be hard drawn copper;
  2. Neutral conductor shall be annealed copper and insulated or non-insulated as required;
  3. Concentric wires shall be annealed copper and insulated;
  4. *:Inner sheath of multi-core cable,two options based on client requirement, a) wrapping tape b) extrusion PVC inner sheath;

PDF Download

PDF Download

Why Choose Us

chanpin-why

Contact Us Immediately

Contact Us

Product Category

hot-sale product

Including 1, 2, 3, 4, 5, 1+1, 2+1, 3+1, 4+1 cores and so on, from 10mm2 to 240mm2 as follows, 10mm2 16mm2 25mm2 35mm2 50mm2 70mm2 95mm2 120mm2 150mm2 185mm2 240m2.

Conductor: 1350-H19 Aluminum conductor, H68 round stranded conpressed(RM) Aluminium Conductor
Insulation: XLPE or PE or PVC, UV-resistant.

XLPE covered aerial cables to AS/NZS 3675.

Water-blocked aluminium alloy 1120 conductors.

Also available with XLPE/HDPE covering.

CU/PVC, AAC/PVC, AAAC/PVC, CU/PE, AAC/PE, AAAC/PE
CU/XLPE, AAC/XLPE, AAAC/XLPE
AAC/PVC, AAC/PE, AAC/XLPE

Duplex/Triplex/Quadruplex Service Drop Cable
Aluminum Overhead Service Drop Cable
LV Overhead insulated Cable
Overhead Service Cable
Overhead Line & Transmission Cables

Contact Us Immediately